Labeled cyber-physical dataset for distribution-grid management includes six OT attack scenarios
The authors claim Data4Cyber provides a realistic, labeled dataset for evaluating intrusion detectors on distribution-grid OT traffic
Security & privacy arXiv 10 Nov 2026 Benchmark Prototype evidence
Published as “Data4Cyber: Labeled Cyber-Physical Datasets for Distribution-Grid Management Systems Under Representative OT Attacks”
Why it matters
Data4Cyber provides a realistic benchmark for developing and testing process-aware, physics-informed IDSs for DER-rich distribution-grid management.
Summary
The paper introduces Data4Cyber, a labeled cyber-physical dataset for DER-centric distribution-grid management that combines real hardware, Modbus/TCP and MQTT traffic, and phase-resolved attack labels. Baseline IDS evaluation shows that under a chronologically blocked split, F1 scores range from 0.649 to 0.813 but with high false-positive rates, indicating the dataset is challenging. A process-aware detector achieves comparable F1 (0.654) with a much lower false-positive rate (0.111) than other methods, highlighting the need for physics-informed detection. The evidence is limited to 30-minute lab runs and does not cover longer-term or larger-scale grid conditions.
What they found 2
- Baseline supervised detectors achieve F1 between 0.649 and 0.813 but with high false-positive rates.
“Under the blocked supervised split, F1 ranges from 0.649 to 0.813, with high false-positive rates.”
- The process-aware baseline attains low false-positive rate (0.111) while maintaining comparable F1 to the best supervised model.
“process-aware baseline is the only S0-trained detector combining low false-positive rate with non-trivial recall, and its F1 is comparable to blocked Extra Trees (0.654 vs. 0.649) at far lower false-positive rate (0.111 vs. 0.873).”
Caveats 4
- existence- and histogram-style detectors reach recall near one at false-positive rates of 0.63-0.64
- The controlled 30-minute laboratory runs intentionally favor traceable cause-effect attribution; broader diurnal, seasonal, and multi-feeder variation remains an extension target rather than a claimed coverage dimension.
- Data4Cyber is recorded in a controlled laboratory setting with vendor-specific Modbus and MQTT semantics.
- The scenario scope focuses on the OT-side manipulation and physical-integrity phase of the attack chain. IT-stage precursors such as phishing, credential theft, or ransomware delivery are outside the measured scenario scope.
What’s new here 4
- Real DER hardware (PV inverters, battery storage) integrated with OT protocols.
- Mixed Modbus/TCP and MQTT traffic with synchronized physical measurements.
- Phase-resolved labels linking cyber events to physical impact.
- A baseline evaluation exposing detection difficulty and false-positive trade-offs.