LLM training workloads can induce megawatt-scale power oscillations in multi-tenant data centers
Renting workstations to run synchronized unoptimized LLM training can create periodic power oscillations that saturate generator control limits
Systems arXiv 18 Nov 2026 Attack Prototype evidence
Published as “Rented Oscillations: Multi-Tenant Data Center Workload Synchronization Attacks and Mitigation”
Why it matters
Grid operators can substantially lower forced-oscillation risk by coordinating tenant workloads, reducing the need for costly grid-side hardware upgrades.
Summary
Multi-tenant data centers can generate large low-frequency oscillations that destabilize the grid, and the authors show that a signal-energy-based detection plus a workload-interleaving mitigation can cut the RMS oscillation of a 1 GW-scale facility by up to 84%, flattening demand. Evidence comes from hardware-in-the-loop experiments on a supercomputer, PHIL tests with a 1 GW emulated DC, and real-time simulations on a 799-bus Saudi Arabian network, all showing substantial reduction in oscillation magnitude.
What they found 5
- Mitigation reduces RMS oscillation of a 1 GW facility by 84%
“reducing the RMS oscillation of the facility demand from 199 to 31 MW (84%) and that of the Riyadh City14 frequency from 67 to 20 mHz (70%).”
- Optimally delayed in-phase workloads cancel almost entirely, cutting RMS from 30.7 MW to 4.6 MW
“optimally delayed, they cancel almost entirely, reducing the RMS oscillation from 30.7 to 4.6 MW.”
- Interleaving three dominant workloads lowers RMS from 26.6 MW to 17.3 MW and cuts critical-band amplitude by 88%
“reducing the RMS oscillation of the facility demand from 26.6 to 17.3 MW and its amplitude in the critical band by 88%.”
- Coordinated mitigation across two geographically distributed DCs cuts bus voltage RMS oscillations by up to 76% (median 61%)
“reduces the RMS voltage oscillation of the 47 target buses by 47-76%, with a median of 61%, and that of bus 375 by 68%.”
- Mitigation remains effective for workload jitter up to 3% and still reduces energy by 40-50% at 10% jitter
“the mitigation retains its full effect for jitter up to 3% and still reduces the oscillation energy by 40% to 50% at 10%.”
Caveats 4
- The resulting peak-to-peak oscillation of 0.2 V is modest, reflecting the small share of computing power acquired and the energy-storage buffers...
- The capability of the adversary is therefore bounded at about 5 Hz, with controllability highest at intermediate duty ratios (40-60 %) and lowest at the extremes.
- trading throughput for a substantially smoother demand
- the mitigation retains its full effect for jitter up to 3% and still reduces the oscillation energy by 40% to 50% at 10%
What’s new here 4
- Combined small- and large-signal analysis with a hardware-grounded DC workload model to locate oscillatory weak points.
- Identification of MW-scale forced oscillations that can saturate generator control limiters and create lightly damped modes via Floquet analysis.
- Signal-energy-based detection that attributes irregularities to individual workloads without inferring intent.
- A workload-interleaving mitigation algorithm that retimes workloads to cancel oscillations, validated on PHIL and large-scale grid simulations.