ICSSPulse discovers and manipulates industrial services, auto-generates executive reports
The authors claim their platform can discover active ICS services, enumerate assets, manipulate process variables, and produce LLM-generated mitigation reports
Security & privacy arXiv 24 Feb 2026 Method Prototype evidence
Published as “ICSSPulse: A Modular LLM-Assisted Platform for Industrial Control System Penetration Testing”
Why it matters
The platform gives educators and researchers a ready-to-use, open-source environment for hands-on protocol-level penetration testing and automated report generation, accelerating training and reproducible studies.
Summary
ICSSPulse can automatically discover, enumerate, and read/write Modbus and OPC UA services in simulated industrial testbeds, and generate structured technical and executive reports using an integrated LLM. The evaluation showed successful identification of Modbus devices on ports 5002 and 502, correct handling of anonymous OPC UA connections, and proper read/write manipulation of simulated process values, with the LLM producing two report formats. Evidence is limited to small-scale lab simulations (a Python Modbus server, a Factory I/O water-treatment scenario, and a custom OPC UA server).
What they found 4
- ICSSPulse identified active Modbus services on both testbeds.
“ICSSPulse successfully identified active Modbus services, with the PyModbus server operating on port 5002 and the water treatment plant using the default Modbus port 502, confirming the presence of Modbus devices in the simulated OT network.”
- The OPC UA handler recognized anonymous access and no security policy.
“the handler correctly identified that the server accepted anonymous connections and operated under a None security policy.”
- The LLM reporting module consolidated scan and exploitation data for GPT-4o-mini.
“The module successfully consolidated the resulting network scan data, enumeration logs, and records of successful read/write exploitation into a unified context for feeding the GPT-4omini model.”
- Write operations on the simulated fill valve were correctly scaled.
“writing an arbitrary value 500 to the fill valve register resulted in a value of 5 due to the water tank’s 100-scale configuration.”
Caveats 4
- ICSSPulse’s reliance on Python-based execution, containerized auxiliary tools, and software-only, unauthenticated testbeds constrains performance and experimental fidelity, rendering the platform suitable only for small-to-medium-scale laboratory environments.
- ICSSPulse’s reliance on Python-based execution, containerized auxiliary tools, and software-only, unauthenticated testbeds constrains performance and experimental fidelity, rendering the platform suitable only for smallto medium-scale laboratory environments.
- ICSSPulse does not model physical disruptions, controller reprogramming, multi-stage ICS kill chains, or privileged engineering workstation attacks. Similarly, Denial of Service (DoS) targeting device availability, packet flooding, or resource exhaustion attacks are outside the platform’s use.
- automated vulnerability scoring is not included in the current version of ICSSPulse
What’s new here 4
- Combines network scanning, protocol-aware enumeration, exploitation, and LLM-assisted reporting in a single web-based platform.
- Provides modular handlers for both Modbus and OPC UA with a unified GUI.
- Introduces an LLM-powered reporting engine that aggregates scan and exploitation artifacts into technical and executive reports.
- Designed for easy extension to additional industrial protocols via plug-in modules.